Overhead Copper wire

Overhead Copper wire

This wire is used on relatively short spans, particularly low & medium voltage
distribution line, in more severe weather conditions.

Standard: BS 7884

Cable Specifications Table
Nominal Area (mm²) Construction Conductor (No-mm) Overall Diameter (mm) Approx. Conductor Weight (mm) Conductor Resistance At 20°C (Ω/km) Minimum Breaking (kN)
10 7 x 1.35 4.05 90 1.806 4.1
16 7 x 1.70 5.1 143 1.1385 6.5
25 7 x 2.10 6.3 219 0.7461 9.9
35 7 x 2.50 7.5 310 0.5264 14
50 7 x 3.0 9 447 0.3656 20.2
50 19 x 1.78 8.9 438 0.3759 19.8
70 19 x 2.10 10.5 597 0.2762 26.9
95 20 x 2.50 12.5 846 0.1949 38.1
120 20 x 2.80 14 1061 0.1554 47.8
150 37 x 2.25 15.7 1337 0.1238 60.1
185 37 x 2.50 17.5 1651 0.1003 74.2
240 61 x 2.25 20.2 2208 0.0753 99.1